Worcester Bosch 24i RSF Fault codes & diagnostics

37 fault codes with plain-English explanations, severity ratings, DIY guidance, and repair cost estimates.

Combi Natural GasLPG 24 kW 1994-2001 Discontinued
GC Number 47-311-28

Replaced by: Greenstar 24i

Download the Worcester Bosch 24i RSF manual The official installation & service manual (PDF) — the exact document these fault codes were verified against. PDF

This boiler uses indicator light combinations

Note which lights are on, off, or flashing and at what speed. Match the combination to the cards below. Do not reset until you have noted the pattern. How to read fault codes →

Severity at a glance

Each cell = one fault code. Hover to identify.
9 Emergency 24 High 4 Medium

All 37 documented codes

Tap any card for details

Flashing mains LED

Your boiler has detected an internal sensor failure and has stopped working to prevent damage or overheating.

High Engineer only £120-£200

Parts commonly replaced

  • NTC Thermistor
  • Wiring Harness
  • Main Circuit Board (PCB)
INDICATOR LIGHT FLASHING

Your boiler has detected a problem with one of its internal temperature sensors and has stopped working as a safety precaution.

High Engineer only £120-220

Parts commonly replaced

  • NTC Temperature Sensor
  • Wiring Harness
  • Main Control Board
299-357

Your boiler has detected an electrical fault involving a blown fuse on the internal control board, which prevents the unit from starting safely.

High Engineer only £120-250

Parts commonly replaced

  • Main printed circuit board (PCB)
  • Internal fuses
299-360

Your boiler's external or built-in heating timer is experiencing a communication or hardware malfunction, preventing it from correctly signalling when the heating should turn on or off.

Medium Engineer only £120-220

Parts commonly replaced

  • Mechanical Timer
  • Programmer Unit
  • Wiring Loom
299-363

Your boiler is struggling to detect the flow of water through the system, which means it cannot safely turn on your heating or hot water.

High Engineer only £150-250

Parts commonly replaced

  • Flow Turbine
  • Hall Effect Sensor
  • Flow Switch
299-495

Your boiler has lost the signal from the sensor that monitors your hot water temperature, meaning the system cannot accurately heat your taps.

Medium Engineer only £120-200

Parts commonly replaced

  • Domestic Hot Water (DHW) NTC Thermistor
  • Wiring harness
324-822

Your boiler's intake filter is blocked or restricted, preventing the fan from pulling in the correct amount of air for safe combustion.

High Engineer only £120-200

Parts commonly replaced

  • Gauze filter
  • Fan assembly
  • Air pressure switch
375 697

Your boiler is failing to light the burner because it cannot detect the ignition spark, meaning you currently have no heating or hot water.

High Engineer only £150-250

Parts commonly replaced

  • Spark electrode
  • Ignition lead
  • Ignition transformer
375 699

Your boiler has detected that the internal safety valve meant to release excess pressure has been triggered, which often causes water to leak or drip from the pipe outside your home.

Emergency Engineer only £180-350

Parts commonly replaced

  • Pressure Relief Valve (PRV)
  • Expansion Vessel
  • Pressure Gauge
AIR FLOW DEVICE

Your boiler has detected an issue with the internal fan or the way it clears exhaust gases, so it has shut down to keep you safe.

High Engineer only £150-350

Parts commonly replaced

  • Fan assembly
  • Air pressure switch
  • Venturi/flue pipe
Showing 11–20 of 37
E00-741

Your boiler is detecting an issue with the fuel supply or the internal gas pressure, which has caused it to stop working to keep your home safe.

Emergency Engineer only £150-300

Parts commonly replaced

  • Gas valve
  • Gas injector
  • Gas supply pipework
E01-579

Your boiler has detected that it cannot ignite or maintain the flame necessary to heat your water or home safely.

Emergency Engineer only £150-350

Parts commonly replaced

  • Ignition electrode
  • Gas valve
  • Printed Circuit Board (PCB)
E01-580

Your boiler is failing to ignite its burner, which means it cannot produce any heat or hot water because it has detected an issue with the fuel or ignition process.

Emergency Engineer only £150-350

Parts commonly replaced

  • Ignition electrode
  • Gas valve
  • Printed Circuit Board (PCB)
E01-591

Your boiler has detected an issue with the way fuel is being supplied to the burner, which means it has safely shut itself down to prevent it from running incorrectly.

Emergency Engineer only £150-300

Parts commonly replaced

  • Gas valve
  • Burner injector
  • Gas pressure regulator
E01-596

Your boiler is failing to detect the airflow needed for safe operation, so it has shut itself down to prevent ignition.

High Engineer only £150-250

Parts commonly replaced

  • Air Pressure Switch
  • Flue Fan
  • Venturi/Pressure Tube
E01-598

Your boiler is failing to light the flame because the internal electrical connection responsible for triggering ignition is likely faulty or disconnected.

High Engineer only £120-220

Parts commonly replaced

  • Ignition lead
  • Ignition electrode
  • Printed Circuit Board (PCB)
E01-599

Your boiler has detected an internal issue with how heat is transferred between the burner and your water, meaning it has shut itself down to prevent damage.

High Engineer only £250-450

Parts commonly replaced

  • Primary heat exchanger
  • Flow sensor
  • NTC thermistor
E01-600

Your boiler has detected an issue with the protective insulation lining inside the combustion chamber, which is a safety-critical part that keeps the heat contained.

Emergency Engineer only £180-350

Parts commonly replaced

  • Insulation pack
  • Combustion chamber seal

Related codes

E01-601

Your boiler is struggling to remove trapped air from the system, which can prevent heat from circulating properly to your radiators.

Medium Engineer only £120-220

Parts commonly replaced

  • Automatic Air Vent
  • Pump Head

Related codes

E01-602

Your boiler's water circulation pump or its electrical connection has failed, meaning your heating and hot water cannot function because the system can no longer push hot water around your radiators and taps.

High Engineer only £250-450

Parts commonly replaced

  • Central heating pump
  • Wiring harness
  • Pump head
Showing 21–30 of 37
E01-603

Your boiler's built-in pressure tank is no longer able to manage the expansion of water as it heats up, which is causing your system pressure to fluctuate and force the boiler to shut down.

High Engineer only £250-450

Parts commonly replaced

  • Expansion Vessel
  • Flexi-hose connection
E01-604

Your boiler's internal computer is experiencing a communication error and is unable to safely coordinate the heating and hot water process.

High Engineer only £250-450

Parts commonly replaced

  • Main PCB
  • Wiring harness
E01-605

Your boiler is struggling to detect or control the flow of hot water, which likely means you will have no hot water coming out of your taps or shower.

High Engineer only £150-250

Parts commonly replaced

  • DHW Flow Turbine
  • Hall Effect Sensor
E01-606

Your boiler has detected that the internal fan responsible for safely venting exhaust gases is not spinning or operating correctly, causing the system to shut down for safety reasons.

High Engineer only £250-450

Parts commonly replaced

  • Fan assembly
  • Printed Circuit Board (PCB)
E01-607

Your boiler has detected that it is running too hot and has automatically switched itself off to prevent potential damage or overheating.

High Engineer only £150-250

Parts commonly replaced

  • High limit thermostat
  • NTC sensor
  • Primary heat exchanger
  • Pump
E01-610

Your boiler has detected an issue with the internal seals designed to keep combustion gases trapped safely inside the unit.

Emergency Engineer only £180-350

Parts commonly replaced

  • Combustion chamber seal kit
  • Gasket pack
E01-612

Your boiler has failed to ignite because it cannot detect a flame, meaning it has safely shut itself down to prevent gas from building up.

High Engineer only £120-250

Parts commonly replaced

  • Flame rectification probe
  • Ignition electrode
  • PCB
E01-886

Your boiler is failing to detect the flow of water needed to fire up and provide heating or hot water.

High Engineer only £150-250

Parts commonly replaced

  • Flow switch assembly
  • Flow turbine
  • Diverter valve diaphragm
E01-892

Your boiler is failing to ignite because it cannot correctly access or regulate its gas supply.

Emergency Engineer only £250-450

Parts commonly replaced

  • Gas valve
  • Printed circuit board (PCB)
E01-893

Your boiler is failing to ignite because it cannot draw the gas supply it needs to stay running.

Emergency Engineer only £180-350

Parts commonly replaced

  • Gas valve
  • Ignition lead
Showing 31–37 of 37
E01-900

Your boiler has detected a loose or faulty temperature sensor connection, meaning it does not know how hot the water is and has safely shut down to prevent overheating.

High Engineer only £120-220

Parts commonly replaced

  • NTC Temperature Sensor
  • Wiring Harness
E01-930

Your boiler has stopped working because it cannot detect a flame, meaning it is currently unable to safely ignite fuel for your heating and hot water.

High Engineer only £120-250

Parts commonly replaced

  • Ionisation electrode
  • Ignition lead
  • PCB
E04-582

Your boiler is struggling to read its own water temperature, so it has safely shut itself down to prevent potential overheating.

High Engineer only £150-250

Parts commonly replaced

  • NTC Temperature Sensor
  • Wiring harness
E05-341

Your boiler is struggling to manage the water pressure within the system, which typically means a small internal pressure-balancing component is failing or requires adjustment.

Medium Engineer only £150-250

Parts commonly replaced

  • Mini Expansion Vessel
  • Pressure Relief Valve
IGNITION LOCKOUT

Your boiler has failed to start up or stay burning, so it has purposefully shut itself off to prevent gas from building up.

High Engineer only £150-350

Parts commonly replaced

  • Ignition electrode
  • Gas valve
  • Printed Circuit Board (PCB)
No mains LED

Your boiler has completely lost power and is unable to turn on, likely due to a blown fuse or a failure in the electrical control board.

High Engineer only £150-350

Parts commonly replaced

  • Internal boiler fuse
  • Printed Circuit Board (PCB)
OVERHEAT CUT-OFF

Your boiler has detected that it got too hot and has automatically shut itself down to prevent damage or fire risk.

High Engineer only £120-250

Parts commonly replaced

  • Overheat thermostat
  • Central heating pump
  • Diverter valve
  • Heat exchanger

11 operating states & engineer diagnostics

Not faults — these are normal operating states. Tap to expand.

299-506 Diagnostic Your boiler is struggling to accurately read or maintain the necessary water pressure system to function effectively. E01-058 Diagnostic Your boiler has detected an issue with the pipes that vent exhaust gases outside, meaning it has safely shut down to prevent the buildup of fumes indoors. E01-059 Diagnostic Your boiler's flue assembly is configured using a specific 45-degree elbow piece, which is a structural setting rather than an active fault. E01-940 Diagnostic Your boiler has detected that it is currently set up for a different type of gas fuel than it is receiving, which prevents it from operating safely. E01-941 Diagnostic Your boiler has identified a mismatch in the fuel settings, indicating that the internal configuration does not match the gas supply type it is currently receiving. E01-942 Diagnostic Your boiler is struggling to clear exhaust fumes or draw in fresh air due to an issue with the pipe that goes through your wall to the outside. E01-943 Diagnostic Your boiler is having trouble venting exhaust gases correctly, likely because the external flue pipe configuration is not communicating properly with the sensors. E01-944 Diagnostic Your boiler is struggling to clear exhaust gases due to an issue with the pipes that lead to the outside, which is preventing the system from running safely. E01-945 Diagnostic Your boiler has detected an issue with the pipes that vent exhaust gases outside, meaning it cannot safely clear its fumes. E01-946 Diagnostic Your boiler has detected an internal issue with how a component is physically secured, which is preventing it from operating safely. F2 1.25AT Diagnostic Your boiler has stopped working because an internal electrical fuse has blown, cutting off the power needed for it to operate.